Powerware UPS Sidecar Powerware 9390 Bedienungsanleitung Seite 56

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 124
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 55
UPS SIDECAR ONELINE DRAWINGS
062806C
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
MAINTENANCE BYPASS CONFIGURATION
80/40, 80/50, 80/60 AND 80/80 kVA,
208/208V AND 480/480V
WITH UPS SERIAL NUMBER SEVENTH DIGIT AT
“A” O R B
K1
K5
K3
UPS Sidecar
MAINTENANCE
BYPASS SWITCH
(MBP)
AC INPUT
TO BYPASS
A
MAINTENANCE
ISOLATION SWITCH
(MIS)
AC INPUT
TO UPS
E1, E2, E3
SINGLE-FEED
JUMPER
(REMOVE FOR
DUAL-FEED)
E6, E7,
E8, E12
C
AC OUTPUT
TO
CRITICAL LOAD
E4. E5
BAT TERY
CONVER TER
INVERTER
RECTIFIER
NOTE 1. A minimum of two separate feeds with
upstream feeder breakers, or one feed
with two upstream feeder breakers, must
be provided: one for the UPS and one for
the UPS Sidecar bypass input. DO NOT
use one feed or a single feeder breaker to
supply both the UPS and the UPS
Sidecar
.
2. Remove jumper for dual-feed.
3. If the load requires a neutral, a bypass
neutral feeder must be supplied.
SERIAL NUMBER SEVENTH
DIGITAT“A”or“B
1of11
164201546---3
E6, E7, E8
E9, E10, E11
Po werware 9390 UPS CABINET
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-6
Seitenansicht 55
1 2 ... 51 52 53 54 55 56 57 58 59 60 61 ... 123 124

Kommentare zu diesen Handbüchern

Keine Kommentare