Powerware 9330 Bedienungsanleitung Seite 169

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 246
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 168
15--3
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
15.4 Environmental Specifications
Operating Temperature 0to40˚C without derating. The recommended
operating temperature is 25˚C.
Operating Altitude Maximum 1500m (5000 ft) at 40_C without
derating
Storage Temperature --- 2 0 t o + 7 0 ˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
Relative Humidity (operating and
storage)
95% maximum, noncondensing
Acoustical Noise 60 dBA at a 1m distance
EMI Suppression Meets FCC Regulation 47, Part 15, for class A
devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801---2 specifications. Withstands up
to 25 kV pulse w ithout damage and with no
disturbance or adverse effect to the critical load.
System Efficiency at Full Unity
PowerFactorLoadandNominal
Input Voltage
208V Models:
92% in Normal Mode
98% in High Efficiency Mode
480V Models
:
90% in Normal Mode
96% in High Efficiency Mode
600
VModels:
90% in Normal Mode
96% in High Efficiency Mode