DESCRIPTION:
DATE:
DRAWING NO:
11 of 17
SHEET:
REVISION:
D
053001
NOTE: Customer ground, size 1/0, can be
run in any conduit listed in Table R.
POWER WIRING INSTALLATION NOTES
164201300---1
A --- 1 2
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table P. Options Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)
Terminal Function Term i na l Function
Size of Pressure
Termination
Vendor
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
L1 Phase A 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
p
Rectifier Transformer
(
T
B
1
)
L2 Phase B 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
(TB1)
L3 Phase C 1 --- #14 --- #0
Entrelec 2.5-2.9(22-26)
Slotted
AC Input To UPS
B
y
p
a
s
s
T
r
a
n
s
f
o
r
m
e
r
L1 Phase A 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
B
y
p
a
s
s
T
r
a
n
s
f
o
r
m
e
r
(TB1)
L2 Phase B 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
(
)
Ll3 Phase C 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
AC Output from
O
u
t
p
u
t
T
r
a
n
s
f
o
r
m
e
r
X1 Phase A 1 --- #14 --- #0
Entrelec 2.5-2.9(22-26)
Slotted
O
u
t
p
u
t
T
r
a
n
s
f
o
r
m
e
r
to Critical Load
(
T
B
1
)
X2 Phase B 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
(TB1)
X3 Phase C 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
Customer Ground Ground Ground 2 --- #14---#1/0 N/A 5.6 (50) Slotted
Table Q. Options Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)
Terminal Function Term i na l Function
Size of Pressure
Termination
Vendor
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
L1 Phase A 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
p
Rectifier Transformer
(
T
B
1
)
L2 Phase B 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
(TB1)
L3 Phase C 1 --- #14 --- #0
Entrelec 2.5-2.9(22-26)
Slotted
AC Input To UPS
B
y
p
a
s
s
T
r
a
n
s
f
o
r
m
e
r
L1 Phase A 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
Bypass Transformer
(
TB1
)
L2 Phase B 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
(
T
B
1
)
Ll3 Phase C 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- #4 ---#4/0
Entrelec 3.2-3.7(28-33)
6mm
Allen
AC Output from
O
u
t
p
u
t
T
r
a
n
s
f
o
r
m
e
r
X1 Phase A 1 --- #14 --- #0
Entrelec 2.5-2.9(22-26)
Slotted
Output T ransformer
to Critical Load
X2 Phase B 1 --- #14 ---#0
Entrelec 2.5-2.9(22-26)
Slotted
t
o
C
r
i
t
i
c
a
l
L
o
a
d
(TB1)
X3 Phase C 1 --- #14---#0
Entrelec 2.5-2.9(22-26)
Slotted
N Neutral 1 --- #4 ---#4/0
Entrelec 4-6(35-52)
6mm
Allen
Customer Ground Ground Ground 2 --- # 1 4 --- 1 / 0 N/A 5.6 (50) Slotted